Clamp Meters
UNI-T UT278A+ Clamp Earth Ground Tester On sale
Condition: New
Availability:
In Stock
Advance Payment Only
UT270 series can quickly and safely measure the grounding system without disconnecting circuit ground lines or the need of auxiliary electrodes. It can measure resistance from 0.01Ω with a resolution of 0.001Ω. UT275 can also measure leakage current up to 30A. These clamps’double insulation design makes them durable tools for outdoor work and effective in blocking interference from the environment.
SKU: TCBOX5
Ask Price
Features of UNI-T UT278A+ Clamp Earth Ground Tester:
- Auto range
- Data hold
- Data recall
- LCD backlight
- Resistance limit alarm
- Low battery indication
- Auto calibration
Technical Specifications of UNI-T UT278A+ Clamp Earth Ground Tester:
Specifications | Range | UT278A+ |
Certifications | CE, RoHS | |
Category ratings | CAT III 300V | |
Earth Ground Resistance (Ω) | 0.01~0.099Ω | ±(1%+0.01) |
0.1~0.99Ω | ±(1%+0.01) | |
1~49.9Ω | ±(1%+0.1) | |
50~99.5Ω | ±(1.5%+0.5) | |
100~199Ω | ±(2%+1) | |
200~395Ω | ±(5%+5) | |
400~590Ω | ±(10%+10) | |
600~800Ω | ±(20%+20) | |
800~1200Ω | ±(25%+30) | |
Leakage current (A) | 0mA~9mA | ±(2.5%+1mA) |
10mA~99mA | ±(2.5%+5mA) | |
100mA~299mA | ±(2.5%+10mA) | |
0.3A~2.99A | ±(2.5%+0.1A) | |
3A~9.9A | ±(2.5%+0.3A) | |
10A~20A | ±(2.5%+0.5A) | |
Display count | EBTN | |
Jaw opening | 32mm | |
Visual and audible alarm | √ | |
Auto power off | √ | |
Jamming signal recognition | √ | |
Over-range display | √ | |
Data storage | 300 | |
Display type | EBTN | |
Ω+A display | √ | |
General Characterisitics | ||
Power | 1.5V battery (LR6) x 4 | |
Display | 47mm x 28.5mm | |
Product net weight | 1.18kg | |
Product size | 285mm x 85mm x 56mm | |
Standard accessories | Batteries, test ring, English manual | |
Standard individual packing | Gift box, tool box | |
Standard quantity per carton | 1pcs | |
Standard carton measurement | 370mm x 110mm x 300mm | |
Standard carton gross weight | 2.6kg |